FD/MFD Fire Dampers EI: Construction, Test Reports and How to Choose the Right Damper

FD/MFD Fire Dampers EI: Construction, Test Reports and How to Choose the Right Damper

  • 03/11/2026
FD vs MFD fire dampers, what EI ratings mean, GSC damper construction per ISO 21925-1 test reports and how to choose a damper for each location.

Fire dampers are installed in air ducts where they pass through fire-rated walls and floors. In a fire, the damper closes so that flame and smoke cannot travel along the duct into another fire compartment. The two common types are FD, closed by a thermal fuse, and MFD, closed by an electric motor and interlocked with the fire alarm system.

This article explains the difference between FD and MFD, what the EI rating means, how the GSC damper is built according to its fire test reports, and how to choose a damper for each location.

GSC MFD EI120 fire damper at the manufacturing workshop

A batch of GSC fire dampers completed at the workshop, awaiting inspection before shipment.

How do FD and MFD dampers differ?

Criteria FD damper (thermal fuse) MFD damper (motor)
Closing mechanism Thermal fuse melts at 70 °C and a spring pulls the blade closed Spring-return electric motor, closes on signal or on power loss
Activation When the duct air temperature reaches the fuse threshold Signal from the fire alarm panel/BMS, without waiting for heat
Status feedback Optional limit switch Status signal sent back to the control centre
Reopening after closing Replace the fuse and reset by hand Reopens electrically, easy to test periodically
Typical application Ordinary supply/return air-conditioning and ventilation ducts Buildings with interlocked fire alarms: high-rise, factories, hospitals, smoke extract
Cost Lower Higher (motor, control wiring)

Quick rule: if the fire protection design requires the damper to close on a fire alarm signal or to be monitored remotely, choose MFD; use FD for the remaining locations to save cost. The damper type, location and EI rating always follow the approved design documents.

What do EI60, EI120 and EI150 mean?

  • E – integrity: the damper does not crack or open up to let flame and hot gas through; smoke leakage during the fire does not exceed 360 m³/(h·m²) per ISO 21925-1.
  • I – insulation: the face not exposed to fire does not rise above the temperature limit (average ≤ 140 K, maximum ≤ 180 K).
  • The number of minutes (60, 120, 150…) is how long the damper kept both criteria in the test.

The required fire resistance of a fire damper is set in QCVN 06:2022/BXD (and Amendment 1:2023), depending on the fire rating of the wall or floor the duct passes through. The test method for mechanical fire dampers is ISO 21925-1:2018 (equivalent to TCVN 14394-1:2025), run together with TCVN 9311-1.

Fire test reports of GSC dampers

Green Supply (GSC) fire dampers have been tested at two accredited laboratories under ISO 21925-1:2018:

Damper type Sample size (mm) Result Test laboratory Date
FD fuse type (GSC-FD/EI150) 1,700×700×200 EI150, sustained 152 minutes Phuong Nam Fire Protection Technology Co., Ltd (LAS-XD 1646) 08/2025
FD fuse type 1,560×780 EI60, sustained 62 minutes Phuong Nam Fire Protection Technology Co., Ltd (LAS-XD 1646) 03/2025
MFD motorized 1,580×780 EI60 Phuong Nam Fire Protection Technology Co., Ltd 03/2025
MFD motorized (single module) 1,700×850×200 Passed EI134 (EI120 required) Vietnam Institute for Building Materials – VIBM (VILAS 003) 02/2026
MFD combined 1,700×1,700×200 Passed EI121 (EI120 required) Vietnam Institute for Building Materials – VIBM (VILAS 003) 05/2026
FD combined (fuse type) 1,700×1,700×200 Passed EI121 (EI120 required) Vietnam Institute for Building Materials – VIBM (VILAS 003) 05/2026

According to the scope stated in the reports, the results apply to dampers of the same construction and equal or smaller size than the tested sample. That is why GSC tested large samples: a single MFD module up to 1,700×850 mm, and combined assemblies up to 1,700×1,700 mm, remain within the scope of the reports.

Some reports were commissioned by a company in the same group as GSC (Viweco Joint Stock Company); GSC is permitted to use these reports within the group.

See the full set on the Fire protection product certificates page.

Construction of the GSC fire damper

The damper is built to the same construction as the tested sample. Main specifications per the reports:

Component Construction per the fire test reports
Damper body 1.15 mm galvanized steel, U-shaped, 200 mm deep; clad with fire-resistant board per the test report (MgO or 10 mm fire board, density 950–1,000 kg/m³) on both inside and outside faces
Blade Multiple layers of fire-resistant and insulating materials: 10 mm fire board, 20 mm MgO, 0.75 mm galvanized steel layer; all 4 edges coated with Hilti FS-ONE MAX intumescent sealant
Connection flange 35 mm high TDC flange, 1.15 mm galvanized steel
Blade stop Assembled fire board, fixed with self-drilling screws
Closing mechanism – FD V-70 thermal fuse, melting point 70 °C; steel spring
Closing mechanism – MFD Spring-return electric motor mounted on the damper body; galvanized steel drive shaft
Smoke leakage in fire < 360 m³/(h·m²), meets ISO 21925-1

Fabricating the GSC fire damper body clad with fire-resistant board

Fabricating the damper body: 1.15 mm steel clad with fire-resistant board.

GSC MFD fire damper awaiting motor installation

GSC fire damper awaiting motor installation and operation check.

Common mistakes when installing fire dampers

  • Installing the damper far from the fire wall, leaving the duct between damper and wall without fire protection.
  • Leaving the gap around the duct through the wall without fire stopping (fire-resistant silicone, ceramic wool, mortar).
  • Installing a damper of different size or orientation from the tested sample, which voids the report for that location.
  • Leaving no access door to replace the fuse or check the motor.
  • Wiring the MFD with the wrong logic to the fire alarm panel, and not running an interlock test before handover.

Why choose GSC fire dampers?

  • Fire test reports for EI150 and EI60 (FD fuse type), EI134/EI121 (MFD) and FD combined EI121 at accredited laboratories.
  • Large sizes within the reports: single module up to 1,700×850 mm, combined up to 1,700×1,700 mm.
  • 1.15 mm steel body is rigid and holds its shape in a fire.
  • Made in Da Nang and Ho Chi Minh City, with fast delivery to Central Vietnam projects.
  • Complete fire protection system: FD/MFD dampers, EI fire-rated ducts, MgO boards, fire stopping materials.

Batch of GSC fire dampers ready for shipment

A batch of GSC fire dampers completed and ready for shipment.

Fire damper FAQ

How do an MD damper and an MFD damper differ? An MD (motorized damper) is a control damper driven by a motor to open, close or modulate airflow, and has no fire resistance. An MFD is a motorized fire damper that has been tested to an EI rating. Never use an MD in place of an MFD where a duct passes through a fire wall.

Can a damper rated EI120 or EI150 be used where EI60 is required? A damper with a higher fire resistance meets a lower requirement, provided the construction, size and installation stay within the scope of the report. The fire protection design engineer makes the final confirmation.

What about dampers larger than 1,700×850 mm? Use a combined damper assembled from modules, within the report scope up to 1,700×1,700 mm. Larger sizes should be discussed with GSC in advance.

How fast does an MFD close? In testing, the MFD damper closed fully 20–25 seconds after the furnace temperature exceeded 50 °C; on a signal from the fire alarm panel, it closes immediately on command.

Request a fire damper quote

Send your damper size list and EI ratings from the drawings via Zalo/Hotline 0905 604 970 or email gsc.mientrung@gmail.com. GSC quotes with the test report package suited to each size.

View the FD/MFD damper product page · View the fire test reports

Related articles
zalo zalo zalo