What is a VAV Box? Construction, Sizing Table and How to Choose the Right VAV Box

What is a VAV Box? Construction, Sizing Table and How to Choose the Right VAV Box

  • 03/11/2026
What a VAV box is, its construction, operating principle, specification tables and how to size VAV/CAV boxes per the 2026 GSC catalogue, for engineers, MEP contractors and owners.

VAV box (Variable Air Volume box) is a terminal unit in a central air-conditioning system. It automatically adjusts the amount of cold air supplied to each zone according to the actual room temperature. Instead of blowing the same airflow into every room, a VAV box supplies only what each zone needs: lightly occupied rooms do not get over-cooled, the AHU fan runs lighter and the electricity bill goes down.

This article summarizes the construction, operating principle, specification tables and sizing method for VAV/CAV boxes according to the 2026 GSC catalogue, for design engineers, MEP contractors and project owners.

GSC single-duct round VAV box with Belimo controller

GSC single-duct round VAV box with Belimo controller, manufactured at the GSC workshop.

How do VAV boxes and CAV boxes differ?

Criteria VAV box CAV box
Airflow Varies with zone demand Held at a fixed set value
Control Thermostat + controller + flow sensor Controller holds a constant flow, no thermostat needed
Typical applications Offices, hotels, shopping centres, schools, hospitals Fresh-air supply, exhaust, areas needing stable airflow
Energy saving High: AHU fan slows down when load drops Lower

Both lines share the same box body and size table; GSC designates them GSC-VAV.xx and GSC-CAV.xx.

How does a VAV box work?

The thermostat measures room temperature and the differential-pressure sensor measures the actual airflow through the inlet. The controller compares it with the setpoint and drives the actuator to open or close the damper. A VAV box works in 3 modes:

  • Cooling: the zone is warmer than the setpoint, so the damper opens wider to supply more cold air (typically about 13 °C from the AHU).
  • Deadband: the temperature is satisfied, so the damper holds minimum airflow (for example 30% open) to keep enough fresh air per ASHRAE 62.
  • Heating (optional): the damper reduces airflow; if an electric reheat coil is fitted, the air is heated before entering the room.

Because it controls on measured airflow, the GSC VAV box is pressure independent: the airflow into the room does not drift when the main duct pressure fluctuates. When many boxes reduce airflow together, the AHU inverter slows the fan to hold duct pressure, which is where the biggest energy saving comes from.

Construction and materials of the GSC VAV box

1. Casing: Mag Shield steel

The box body is made of Zn-Al-Mg alloy-coated steel (Mag Shield). According to the steel manufacturer, this coating resists rust 3–5 times better than ordinary galvanized steel and self-heals at cut edges and drilled holes thanks to its magnesium content, which suits humid and coastal climates such as Central Vietnam.

2. Belimo LMV-BAC-001 ZEM controller and actuator

Parameter Value
Supply voltage AC/DC 24 V, 50/60 Hz (AC range 19.2–28.8 V)
Motor torque 5 Nm, 95° rotation angle
Flow sensor Belimo Δp sensor, 0–500 Pa measuring range, no zero adjustment needed
BMS communication BACnet MS/TP or Modbus RTU; peripherals via MP-Bus or analog/digital I/O
Control loop By room temperature or air quality (CO₂)
Setup and maintenance Built-in NFC antenna, configuration by smartphone
Protection class IP20, SELV (safety extra-low voltage)

Supplied thermostat: Belimo 22RT-A001, with LCD display, sensor accuracy ±0.3 °C (15–30 °C), On/Off/Eco/Boost modes, and CAV switching via app or BACnet. CAV boxes are not supplied with a thermostat.

3. Internal insulation and acoustic lining

  • Thickness 20–25 mm; thermal conductivity 0.0343 W/m·K at 23 °C (ASTM C518).
  • No mould growth (ASTM C1338); operating temperature −80 °C to +100 °C.
  • Fire and smoke performance: Class 0, Class 1; sound attenuation 20 mm at 18 dBA, 25 mm at 21 dBA.

Inspection of round VAV boxes at the GSC workshop in Da Nang

A batch of round VAV boxes at the GSC workshop, with flow-sensor tubing connected, awaiting inspection before shipment.

Specification table for round VAV/CAV boxes (GSC-VAV.xx / GSC-CAV.xx)

Model Size (in) Inlet Ø D (mm) Box W×H×L (mm) Max airflow (m³/h) CFM L/s Outlet A×B (mm) Kg
VAV/CAV.04 4 102 300×200×400 357 210 99 250×150 7
VAV/CAV.06 6 152 300×200×400 850 500 234 250×150 7
VAV/CAV.08 8 203 300×250×400 1,479 870 411 250×200 8
VAV/CAV.10 10 254 360×310×400 2,278 1,340 632 300×260 10
VAV/CAV.12 12 305 400×380×650 3,417 2,010 949 350×330 15
VAV/CAV.14 14 356 500×450×650 4,505 2,650 1,251 450×400 20
VAV/CAV.16 16 406 600×450×760 6,460 3,800 1,793 550×400 25
  • Operating static pressure: 50–250 Pa.
  • Airflow accuracy: ±5% within 20–100% of rated airflow.

Rectangular VAV/CAV boxes (GSC-VAV.W×H)

For rectangular ducts, GSC manufactures to W×H dimensions from 200 to 1,000 mm (100 mm steps), with a box length L = 580 mm. Rated airflow follows the ASHRAE Handbook 2015, Chapter 48: Fmin at a velocity of 2.0 m/s, Fmax per the catalogue table.

Formula for engineers to self-check: Q (m³/h) = W (m) × H (m) × v (m/s) × 3,600. Example, a 500×400 box at 2.0 m/s: 0.5 × 0.4 × 2.0 × 3,600 = 1,440 m³/h.

Size W×H (mm) Fmin at 2.0 m/s (m³/h) Fmax per catalogue (m³/h)
200×200 288 1,440
300×300 648 3,240
400×300 864 4,320
500×400 1,440 7,200
600×500 2,160 10,800
800×600 3,456 17,280
1,000×1,000 7,200 36,000

The full table of 81 sizes is in the GSC VAV/CAV box catalogue.

Fabrication of rectangular VAV boxes at the GSC workshop

Fabrication of rectangular VAV boxes at the GSC workshop.

New: VAV Universal room pressure control

Since the October 2026 catalogue, GSC has added the VAV Universal room pressure line (model GSC-VAV-P.W×H). Instead of controlling on temperature, the box maintains positive or negative room pressure, for cleanrooms, isolation rooms, operating theatres and laboratories.

Component Model Function
Room pressure controller Belimo VRU-M1R-BAC Integrated M1R differential-pressure sensor, −75…+75 Pa range; BACnet MS/TP, Modbus RTU or MP-Bus communication; configuration via Belimo Assistant 2
Actuator Belimo LM24A-VST 5 Nm rotary motor, AC/DC 24 V, quick-connect to the controller; suits dampers up to about 1 m²
Casing Mag Shield steel Corrosion resistant, suits humid environments

How to size a VAV box: 4 steps and a worked example

  1. Determine Vmax and Vmin of the zone from the cooling load and fresh-air requirement (m³/h, L/s or CFM).
  2. Choose a size whose rated airflow is above Vmax, but not excessively so: Vmin must be ≥ 20% of rated airflow for the controller to hold ±5% accuracy.
  3. Check the inlet static pressure is within 50–250 Pa; add a silencer duct after the box if the room requires low noise.
  4. Select options: reheat coil, BMS protocol, and the room pressure line for cleanrooms or isolation rooms.

Example: an office zone needs Vmax = 1,500 m³/h, Vmin = 500 m³/h.

  • Size 10" (rated 2,278 m³/h): Vmax 1,500 < 2,278 ✓; 20% × 2,278 = 456 m³/h ≤ Vmin 500 ✓ → choose size 10".
  • Size 12" (rated 3,417 m³/h): 20% × 3,417 = 683 m³/h > Vmin 500 ✗ → oversized, so at Vmin the controller loses accuracy.

Quick conversions: 1 CFM ≈ 1.699 m³/h; 1 L/s = 3.6 m³/h.

Installation and operation notes

  • Avoid elbows, tees and valves immediately before the inlet: turbulent flow makes the sensor misread airflow.
  • Leave an access door and working space for the controller and actuator.
  • Supply 24 V through a dedicated transformer and wire per the Belimo diagram in the catalogue.
  • Set Vmin/Vmax per the design documents and run air balancing (TAB) before handover.

GSC technician checking a VAV box before shipment

GSC technicians checking sensor connections on a VAV box batch before delivery.

Why choose GSC VAV boxes?

  • Made in Da Nang and Ho Chi Minh City: fast delivery to Central Vietnam projects and lower transport cost.
  • Belimo control components (Switzerland) with BACnet/Modbus, easy to integrate into a BMS.
  • Mag Shield steel body resists corrosion, an advantage for coastal projects.
  • Full size range: round 4"–16", rectangular 200–1,000 mm, plus the room pressure line.
  • Reference projects in the catalogue: Terminal T3 at Tan Son Nhat Airport, Mat Troi (Sun) Hospital in Phu Quoc.
  • Checked before dispatch: each sensor and controller assembly is checked against its parameters before delivery.
  • One-stop supplier: VAV boxes, reheat coils, silencer ducts, air ducts, diffusers.

VAV box FAQ

Must a VAV box connect to a BMS? No. A VAV box can run standalone with its thermostat. BMS connection via BACnet MS/TP or Modbus RTU adds monitoring, scheduling and AHU fan optimization to actual demand.

How much energy does a VAV box save? It depends on the hourly load and the AHU inverter. By the fan law, fan power falls roughly with the cube of speed, so a 20% airflow reduction can cut fan power by almost half (0.8³ ≈ 0.51). Actual figures must be calculated for each project.

When should I use a CAV box instead of a VAV box? When the area needs fixed airflow: fresh-air supply, exhaust, corridors, technical rooms.

Does GSC make rectangular VAV boxes to custom sizes? Yes, from 200×200 to 1,000×1,000 mm in 100 mm steps.

Which type for cleanrooms and isolation rooms? The VAV Universal room pressure line (GSC-VAV-P), which controls on room pressure in the −75…+75 Pa range.

Request a VAV box quote

Send your zone airflow schedule or BOQ via Zalo/Hotline 0905 604 970 or email gsc.mientrung@gmail.com. GSC will select sizes, check Vmin/Vmax and quote the same day.

View the VAV box product page · Download the VAV/CAV box catalogue (PDF)

Related articles
zalo zalo zalo