GSC VAV and CAV boxes made in Da Nang and Ho Chi Minh City: round Ø4"–16", rectangular 200–1,000 mm, Belimo controllers, Mag Shield casing; room-pressure line available.
  • Product code:GSC-VAV
Share:

GSC VAV box / CAV box are terminal units that regulate airflow in central air-conditioning systems: VAV (Variable Air Volume) supplies airflow that varies with each zone's demand, CAV (Constant Air Volume) holds a fixed airflow. GSC manufactures in Da Nang and Ho Chi Minh City, using Belimo controllers and Mag Shield steel casings, with same-day quotes.

GSC round VAV/CAV box with flow sensor and controller enclosure

Illustration: GSC round VAV/CAV box.

Product lines

Line Model Application
Round VAV box (single duct) GSC-VAV.04 … GSC-VAV.16 Offices, hotels, retail, hospitals
Rectangular VAV box (single duct) GSC-VAV.WxH Large airflow, rectangular section per drawings
CAV box (constant airflow) GSC-CAV.xx Fresh air, exhaust, areas needing steady airflow
VAV Universal – room pressure GSC-VAV-P Rooms with non-critical leakage that need a pressure difference (kitchens, smoking rooms, hospital areas); −75…+75 Pa, Belimo VRU-M1R-BAC controller

Round size table (Ø4"–16")

Size Inlet Ø (mm) Max airflow (m³/h) Weight (kg)
4" 102 357 7
6" 152 850 7
8" 203 1,479 8
10" 254 2,278 10
12" 305 3,417 15
14" 356 4,505 20
16" 406 6,460 25

Rectangular (W, H = 200–1,000 mm, L = 580 mm)

Maximum airflow is calculated at about 10 m/s and minimum at 2.0 m/s (per ASHRAE Handbook 2015, chapter 48): Q (m³/h) = W × H × v × 3,600. Examples: 200×200 mm → 1,440 m³/h; 400×300 mm → 4,320 m³/h; 600×600 mm → 12,960 m³/h; 1,000×1,000 mm → 36,000 m³/h.

GSC rectangular VAV box in powder-coated steel

Illustration: GSC rectangular VAV box.

General specifications

  • Operating static pressure: 50–250 Pa; accuracy ±5% from 20–100% of rated flow.
  • Casing: Mag Shield steel (Zn-Al-Mg), corrosion resistant, suited to humid and coastal climates.
  • Internal acoustic lining: 20–25 mm thick, thermal conductivity 0.0343 W/m·K, no mould growth (ASTM C1338), working temperature −80…+100 °C.
  • Controller / actuator: Belimo LMV-BAC-001 ZEM, 24 V, 5 Nm torque, Δp sensor 0–500 Pa, BACnet MS/TP or Modbus RTU, NFC commissioning.
  • Thermostat (VAV): Belimo 22RT-A001; the CAV box does not include a thermostat.
  • Options: electric reheat coil, acoustic duct, stainless-steel casing.

Why choose GSC VAV/CAV boxes

  • Made in Da Nang and Ho Chi Minh City, giving control of delivery schedules for central and southern Vietnam projects.
  • Belimo control components, easy BMS integration.
  • Sensor and controller parameters are checked before dispatch.
  • Single-supplier coordination: VAV boxes, reheat coils, acoustic ducts, ductwork, diffusers.
  • Reference projects: Tan Son Nhat Airport Terminal 3, Mat Troi (Sun) Hospital in Phu Quoc, Can Tho Stroke Hospital, Binh Duong 1,500-bed Hospital.